Switchgear Tegangan Sedheng
KYN61-40.5 Metalclad AC Tertutup Switchgear, Tipe Withdrawable
KYN61-40.5 Air insulated metal clad switchgear movable yaiku switchgear njero ruangan, dipasang ing kondisi 50/60Hz telung fase lan voltase AC 40.5kV, sing ditrapake kanggo transmisi lan distribusi kanggo generator, gardu transformator lan industri lan tambang. perusahaan.Uga bisa digunakake kanggo ngontrol, nglindhungi lan ngawasi sirkuit listrik, lan migunani banget kanggo kahanan operasi sing kerep.
Standar: IEC62271-200
Pamilihan
kahanan operasi
1. Suhu udara sekitar: -15 ℃ ~ + 40 ℃
2. Dhuwur: ≤1000m
3.Asor relatif: Rata-rata saben dina≤95%;Rata-rata saben wulan≤90% 4. Lindhu 4.intensitas:≤magnitudo 8.
5.Aplikasi ing panggonan tanpa gas korosif lan kobong.
Cathetan: Produk sing disesuaikan kasedhiya.
Fitur
1.Kabinèt digawe saka aluminium-seng dilapisi sheet diproses dening peralatan CNC lan nglumpuk karo bolts utawa rivets, kanthi struktur modular.
2. Switchgear iki nduweni macem-macem fungsi kanggo nyegah misoperations, kalebu nyegah troli dimuat saka obah, nyegah coupling urip lan ngalih earthing, lan nyegah entri ora sengaja menyang kompartemen urip.
3. Switchgear dilengkapi pemutus sirkuit vakum ZN85 kanthi kinerja sing apik lan gerobak tangan, lan busbar utama disambungake tanpa perlu transfer transisi.
4. Switchgear iki majeng, kinerja stabil, struktur cukup, gampang kanggo-
nggunakake, peralatan distribusi daya aman lan dipercaya
Parameter switchgear
Ora. | Item | Unit | Nilai | |
1 | Dirating voltase | kV | 40.5 | |
2 | Rated saiki | A | 630/1250/1600/2000/2500 | |
3 | frekuensi dirating | Hz | 50/60 | |
4 | Frekuensi daya tahan voltase ing 1 min | Fase, Bumi | kV | 95 |
Fraktur isolating | kV | 110 | ||
5 | Tegangan tahan impuls kilat (Puncak) | Fase, Bumi | kV | 185 |
Fraktur isolating | kV | 215 | ||
6 | Rated saiki saka busbar utama | A | 630/1250/1600/2000/2500 | |
7 | Rated saiki busbar cabang | A | 630/1250/1600/2000/2500 | |
8 | Rated short-circuit breaking saiki | kA | 20/25/31.5 | |
9 | Dirating short-time tahan saiki | kA | 20/25/31.5 | |
10 | Rated puncak tahan saiki | kA | 50/63/80 | |
11 | Rated short circuit nggawe saiki | kA | 50/63/80 | |
12 | Frekuensi tahan voltase ing 1 menit saka loop kontrol aux | V | 2000 | |
13 | Uji durasi busur internal (0,5 detik) | kA | 31.5 | |
14 | Degress saka pangayoman | IP | IP4X (IP2X nalika lawang ngarep dibukak) | |
15 | Rated voltase saka aux kontrol loop | V | AC utawa DC 110/220 |
Parameter ZN85-40.5
Ora. | Item | Unit | data | |||
1 | Dirating voltase | kV | 40.5 | |||
2 | Tingkat insulasi sing dirating | voltase tahan impuls kilat (gelombang penuh) | kV | 185 | ||
1 min frekuensi daya tahan voltase | kV | 95 | ||||
3 | frekuensi dirating | Hz | 50 | |||
4 | Rated saiki | kA | 630 | 630/1250 | 1250/1600/2000/2500 | |
5 | Rated short-circuit breaking saiki | kA | 20 | 25 | 31.5 | |
6 | Rated short-circuit nggawe saiki | kA | 50 | 63 | 80 | |
7 | Rated tahan arus (puncak) | kA | 50 | 63 | 80 | |
8 | Dirating short-time tahan saiki | kA | 20 | 25 | 31.5 | |
9 | Wektu istirahat tetep | s | ≤0,07 | |||
10 | Nggawe wektu | Mekanisme elektromagnetik | s | Mekanisme elektro-magnetik≤0.2 | ||
Mekanisme spring | s | Mekanisme spring ≤0.10 | ||||
11 | Urutan operasi sing dirating | / | Bukak-0.3s-tutup mbukak-180s-tutup mbukak | |||
12 | Urip mekanik | kaping | 10000 |
Fitur
Diagram garis tunggal